Technical specifications
|
Property
|
Value
|
Optical sensor Technology
|
IR versions: Si photodiode Spectral response peak @ 920nm
IR versions: Si photodiode Spectral response peak @ 920nm
VL versions: Si photodiode Spectral response peak @ 560nm
UV versions: SiC photodiode Spectral response peak @ 280nm
UVIR version: Si + SiC photodiode1 Spectral response peak @280nm and 920nm
1 Si and SiC photodiodes signals can be processed individually or both combined as per burner opertion
|
Power supply voltage
|
24VDC (-25%, +20% = 18 ÷ 29VDC )
|
Power supply current
|
150mA typical,
|
Power consumption
|
3.6W typical, 4W max
|
Inrush current
|
6A peak, 2ms settling time
|
Flame Relay
Safe Relay
|
Contacts: 1 NO, for each relay
240 VAC / 1.5A cycles ≥ 100,000
240 VDC / 100 mA
30 VDC / 300mA
Minimum load 10mA, 5VDC
|
FFRT
|
Flame Failure Response Time: 0.2s to 4s
|
Analog output (4-20mA)
|
4÷20 mA (R load <= 500Ω)
Galvanically isolated
Precision: +/-5% f.s
|
Digital Inputs, 24 VDC
|
Nr. 2 digital inputs (opto coupled), to allow selection of one out of four different sets of parameters; return signal common to both inputs.
Nominal voltage 24VDC (5 mA typical)
Max Voltage 36 VDC
Off: < 5 VDC
On: > 18 Vdc
|
Communication ports
|
Two, redundant, RS-485 serial channels configurable in Profibus or Modbus protocols.
Profibus: max speed 12 Mbit/s
Modbus: max speed 115.200 bit/s
|
Local configuration interface
|
4 push buttons (UP, DOWN , LEFT, RIGHT)
3-digits LED display
|
Air source for lens cleaning
|
From clean ambient air
|
Air flow for lens cleaning
|
LOS (Line Of Sight) versions: 115 l/min (4 SCFM)
Excessive contaminants might require a flow up to 400 l/min (14 SCFM)
FOC (Fibre Optic Cable) versions: 400 l/min (14 SCFM)
|
Minimum cleaning air pressure
|
LOS (Line Of Sight) versions: 20mm H2O (1” W.C.) above the max wind box pressure measured at the “Y” connection inlet.
FOC (Fiber Optic Cable) versions: 400mm H2O (12” W.C.) above the max wind box pressure measured at the “Y” connection inlet.
|
Maximum fibre optic continuous
operating temperature
|
482° C (900° F) for VL and IR fiber optic cables
350° C (662° F) for UV and dual sensor UVIR fiber optic cable
|
Housing mounting thread
|
1” NPT male
|
Cable entry thread
|
¾ “ NPT female (N/A for connectorized versions)
|
Electrical connections
(terminal versions)
|
Removable terminals with screws
Allowable cable section:
AWG24-AWG12, 0.2-2.5mm2 for Relay contacts (J1 connector)
AWG 28-AWG16, 0,08-1.5mm2 for all other terminals
|